Product Code: 0100-03315
The FireNET FN-4127-IO is a 16 channel Input/Output board that provides powerful input/output expansion & addition to the FireNET system allowing up to thirty two I/O boards to be connected to each FireNET panel within the FireNET network. Every I/O board connected to any panel is available to the entire network, which allows for network wide input/output mapping. Typical uses include graphical LED map displays /annunciators, tabular LED zone display/annunciators, input/output logic to & from the fire system for secondary use (I/O board points cannot be used for primary fire initiation inputs or notification outputs) such as access control, burglar, CCTV, intercom, voice, or other 3rd party systems. Each channel can be configured to produce a variety of input actions or respond to a variety of output
categories or logic.
STANDARD FEATURES
• 16 channels of input/output points
• 32 I/O boards per FireNET panel (512 channels of input/output points)
• Each channel configurable as input or output point
• Inputs are opto-isolated non-supervised pulldown type triggered by “dry” contact from input source
• Outputs are open collector transistor pulldown type (100mA max each) that provide “wet” voltage output
• Simple 4 wire connection to control panel (2 for power, 2 for data)
• All inputs/outputs can be assigned to global functions, any event category, and used in network wide Cause & Effect logic
• Can be mounted locally within control panel enclosure or remotely via FN-ACC accessory enclosure up to 4000ft from the panel
• Each I/O board has a unique address 1-32 (set viaDIP switch) on the I/O Comms Bus
• Input/Outputs are for secondary use, not for primary fire initiation inputs or notification outputs
• Two LED’s are provided for communication status
FN-4127-IO_09-2014.pdf
categories or logic.
STANDARD FEATURES
• 16 channels of input/output points
• 32 I/O boards per FireNET panel (512 channels of input/output points)
• Each channel configurable as input or output point
• Inputs are opto-isolated non-supervised pulldown type triggered by “dry” contact from input source
• Outputs are open collector transistor pulldown type (100mA max each) that provide “wet” voltage output
• Simple 4 wire connection to control panel (2 for power, 2 for data)
• All inputs/outputs can be assigned to global functions, any event category, and used in network wide Cause & Effect logic
• Can be mounted locally within control panel enclosure or remotely via FN-ACC accessory enclosure up to 4000ft from the panel
• Each I/O board has a unique address 1-32 (set viaDIP switch) on the I/O Comms Bus
• Input/Outputs are for secondary use, not for primary fire initiation inputs or notification outputs
• Two LED’s are provided for communication status